Share Categories Channel

1/5
Ahlc-Eb DC Leakage Current Sensor for Solar Insulation 100mA-1A/5V image 1Ahlc-Eb DC Leakage Current Sensor for Solar Insulation 100mA-1A/5V image 2

Ahlc-Eb DC Leakage Current Sensor for Solar Insulation 100mA-1A/5V

Jiangsu Acrel Microgrid Institute Co., Ltd

Price $28.90 / Piece
Mini Order
-+Subtotal: $289
Availability In Stock
Purchase details

Payments:

Returns&Refunds:

Eligible for returns and refunds View More

AHLC-EB
Electromagnetic
Analog Output
Integration
Metal
1.0G
Ad, DSP, PLC, Energy Meter
IP40
IEC, RoHS
Customized
10mA-2A
5V
+15V, -15V
D 60mm
Acrel
Carton
AHLC-EB
China
9030339000
Product Description

DC leakage current sensor applied to photovoltaic insulation
        The leakage current sensor is installed around the positive and negative outgoing lines of the photovoltaic DC circuit. When the device is running, the signal output by each branch sensor is detected in real-time. When the branch insulation is normal, the current flowing through the sensor is equal in magnitude and opposite in direction. The output signal is zero; when the branch is grounded, the leakage current sensor has a differential current flowing, and the output of the sensor is not zero. Therefore, by detecting the output signal of each branch sensor, the grounding branch of the photovoltaic DC system can be judged. This principle has high precision in line selection and is not affected by the distributed capacitance of the line.

Specification

SpecificationRated currentPower supplyRated outputAperturePrecision
AHLC-LTADC 10mA~2A±15V5Vφ20mm1
AHLC-EADC 10mA~2A±15V5Vφ40mm1
AHLC-EBDC 10mA~2A±15V5Vφ60mm1

 

Product Parameters

AHLC-EB 
ItemParameter
Rated Input Current±10~±2000mA
Rated Output Voltage±5V
Accuracy1
Supply Power VoltageDC±15V(±20%)
Zero offset voltage±20mV
Offset voltage drift≤±1.0mV/ºC
Linearity≤0.3%FS
Response time≤300ms
Insulation voltage2.5kV/50Hz/1min
Working Temperature-40'ºC~85'ºC
Storage Temperature-40°ºC~85ºC
Power consumption≤0.5W

 

Dimension


Size
Spec.

 
Outline size(mm)Through size(mm)Mounting size(mm)Figure
WHDΦ2Φ1MN
AHLC-LTA68572050205252Fig.1
AHLC-EA10010830754078/Fig.2
AHLC-EB12011230946098/Fig.3
Notes:
1. When the hall sensor is used, in order to obtain better dynamic characteristics and sensitivity, attention must be paid to the coupling between the primary side coil and the secondary side coil. It is recommended to use a single wire and the wire completely fills the hall sensor module wire hole;
2. When the hall sensor is used, the best measurement accuracy can be obtained under the rated input current value. When the measured current is far lower than the rated current To obtain the best accuracy, multiple turns can be used for the primary side, i.e. IPNP = rated ampere-turns. In addition, the temperature of the primary side feeder shall not exceed 80 ºC;
3. The auxiliary power supply of the Hall current sensor shall not exceed ± 20% of the calibrated value when it works normally;
4. Hall current sensor shall not fall from a high place (≥ 1m) during installation and use;
5. It is unable to adjust the zero point and full degree adjustment potentiometer;
6. Auxiliary power supply needs to be configured by itself;
7. The positive and negative poles of the power supply cannot be reversed

Wiring

 

Installation Instructions

After Sales Service

Certifications

 

Company Profile

Acrel Co., Ltd.[stock code: 300286.SZ] is a high-tech enterprise that integrates R&D, production, sales, and service, since its establishment, is committed to providing users with energy efficiency management and powerful security system solutions. Acrel Electric has a complete production line from cloud platform software to sensors.
Acrel energy efficiency management system including substation operations and maintenance cloud platform, electricity safety management cloud platform, Environmental equipment power consumption monitoring cloud platform, prepaid management (system) cloud platform, intelligent power distribution monitoring system, power quality management system, building energy consumption management system, industrial energy control platform, leakage power monitor and control system, fire-fighting device power monitoring system, fire-proof door monitoring system, emergency lighting and evacuation indicating system, EV charger management system, data center power&environment monitoring system, smart lighting control system, IT isolation power supply system and related products.
The company attaches great importance to product quality and innovation. By the end of 2018, the company has 5 trademarks, 18 invention patents, 72 utility model patents, 94 appearance patents, and 147 computer software Copyrights, and has participated in the formulation of national or industrial standards.
 

Send Message

Content*

Your Name

Tel*

Email*

Shop Cart